Wire Gauge Calculator

Turn an AWG gauge into mm² and diameter, or find the AWG for a metric size, a diameter or a stranded wire. Advanced adds copper and aluminium resistance at any temperature, weight and turns per inch.

More options
Start from

A smaller number is a thicker wire. Every 3 gauges halves the area; every 6 gauges halves the diameter.

Resistance and weight
m
°C

Length of one wire (a circuit out and back is twice the run). Resistance rises about 0.4% per °C; 20 °C is the reference, and a loaded cable often runs at 60–90 °C.

ResultUpdates as you type—Cross-section area—Diameter—Diameter in inches—Circular mils—Nearest metric size—Nearest AWG—Copper resistance at 20 °C—Copper at your temperature—Aluminium at your temperature—Resistance of your length—Weight—Turns per inch, close wound

No current ratings here. How many amps a wire can safely carry (its ampacity) depends on your wiring code, the insulation, how it is installed and bunched, and the room temperature, so it isn't shown. Check your local rules or an electrician, and use the voltage drop calculator for long runs.

Full AWG table, 4/0 to 40
AWGDiameter inDiameter mmArea mm²Circular milsCopper Ω/kmCopper Ω/1000 ftCopper kg/km
4/0 AWG0.4611.684107.2211,6000.16080.04901960.7
3/0 AWG0.409610.40585.03167,8060.20280.0618761.9
2/0 AWG0.36489.26667.43133,0770.25570.07793604.2
1/0 AWG0.32498.25153.48105,5350.32240.09827479.1
1 AWG0.28937.34842.4183,6930.40650.1239380
2 AWG0.25766.54433.6366,3710.51260.1562301.3
3 AWG0.22945.82726.6752,6350.64640.197239
4 AWG0.20435.18921.1541,7410.81510.2484189.5
5 AWG0.18194.62116.7733,1021.0280.3133150.3
6 AWG0.1624.11513.326,2511.2960.395119.2
7 AWG0.14433.66510.5520,8181.6340.498194.52
8 AWG0.12853.2648.36616,5102.0610.628174.96
9 AWG0.11442.9066.63413,0932.5990.792159.44
10 AWG0.10192.5885.26110,3833.2770.998847.14
11 AWG0.09072.3054.1728,2344.1321.25937.38
12 AWG0.08082.0533.3096,5305.211.58829.65
13 AWG0.0721.8282.6245,1786.572.00323.51
14 AWG0.06411.6282.0814,1078.2852.52518.64
15 AWG0.05711.451.653,25710.453.18414.79
16 AWG0.05081.2911.3092,58313.174.01511.73
17 AWG0.04531.151.0382,04816.615.0639.299
18 AWG0.04031.0240.8231,62420.956.3857.374
19 AWG0.03590.9120.65271,28826.418.0515.848
20 AWG0.0320.8120.51761,02233.3110.154.638
21 AWG0.02850.7230.41058104212.83.678
22 AWG0.02530.6440.325564252.9616.142.917
23 AWG0.02260.5730.258250966.7820.352.313
24 AWG0.02010.5110.204740484.2125.671.834
25 AWG0.01790.4550.1624320106.232.371.455
26 AWG0.01590.4050.1288254133.940.811.154
27 AWG0.01420.3610.1021202168.851.460.9149
28 AWG0.01260.3210.08098160212.964.890.7255
29 AWG0.01130.2860.06422127268.581.830.5754
30 AWG0.010.2550.05093101338.5103.20.4563
31 AWG0.00890.2270.0403979.7426.9130.10.3619
32 AWG0.0080.2020.0320363.2538.3164.10.287
33 AWG0.00710.180.025450.1678.8206.90.2276
34 AWG0.00630.160.0201439.8855.9260.90.1805
35 AWG0.00560.1430.0159731.51,0793290.1431
36 AWG0.0050.1270.01267251,361414.80.1135
37 AWG0.00450.1130.0100519.81,716523.10.09001
38 AWG0.0040.1010.00796715.72,164659.60.07138
39 AWG0.00350.090.00631812.52,729831.70.05661
40 AWG0.00310.080.005019.93,4411,0490.04489

Worked out from the AWG formula and copper's standard resistivity at 20 °C (1.724 × 10⁻⁸ Ω·m) and density (8.96 g/cm³), for solid round wire.

How your wire size is worked out

Turn the gauge into a diameter, the diameter into an area, then match that area to the nearest standard sizes.

  1. 1

    Diameter

    0.005 in × 92^(24÷39)= 2.053 mm

  2. 2

    Cross-section

    π ÷ 4 × 2.053²= 3.309 mm²

  3. 3

    Circular mils

    80.81 mil × 80.81= 6,530 cmil

  4. 4

    Nearest sizes

    metric: 4 mm²AWG: 12 AWG

Read more: the formula, a worked example, resistance, weight, stranded wire and the full AWG table

American Wire Gauge (AWG) is a geometric series: 4/0 is fixed at 0.46 inch, 36 AWG at 0.005 inch, and there are 39 equal steps between them, each about 12.3% thinner than the last. Metric cables are named straight by their metal area in mm². To compare the two, turn the gauge into a diameter, the diameter into an area, then look for the closest size in the other system.

The formula

diameter in inches = 0.005 × 92 ^ ((36 − AWG) ÷ 39)
diameter in mm = 0.127 × 92 ^ ((36 − AWG) ÷ 39)
(use 0, −1, −2, −3 for 1/0, 2/0, 3/0, 4/0)
area in mm² = π ÷ 4 × diameter in mm²
circular mils = (diameter in mils)², 1 kcmil = 1,000 circular mils = 0.5067 mm²
gauge from a diameter = 36 − 39 × log(diameter in mm ÷ 0.127) ÷ log(92)
stranded area = number of strands × π ÷ 4 × strand diameter²
resistance per metre = resistivity × (1 + α × (temperature − 20)) ÷ area
weight per metre in grams = density in g/cm³ × area in mm²

Standard values used: copper resistivity 1.724 × 10⁻⁸ Ω·m and α = 0.00393 per °C; aluminium 2.82 × 10⁻⁸ Ω·m and α = 0.00403 per °C (both at 20 °C). Density: copper 8.96 g/cm³, aluminium 2.70 g/cm³.

Worked example

12 AWG, the page's starting value, with 100 m of wire at 20 °C.

  • Diameter: 92 ^ ((36 − 12) ÷ 39) = 92 ^ 0.61538 = 16.16162, so d = 0.005 × 16.16162 = 0.08081 in = 0.08081 × 25.4 = 2.053 mm = 80.81 mils.
  • Area: π ÷ 4 × 2.052525² = 0.785398 × 4.212860 = 3.309 mm².
  • Circular mils: 80.808² = 6,530 cmil = 6.530 kcmil.
  • Nearest metric size: 3.309 mm² sits between 2.5 and 4 mm². 4 ÷ 3.309 = 1.21 is closer than 3.309 ÷ 2.5 = 1.32, so the nearest is 4 mm², which is also the next size up.
  • Copper resistance: 1.724 × 10⁻⁸ ÷ 3.308773 × 10⁻⁶ = 0.0052104 Ω/m = 5.210 Ω/km = 5.2104 × 0.3048 = 1.588 Ω/1000 ft. 100 m: 0.5210 Ω.
  • Aluminium the same size: 2.82 × 10⁻⁸ ÷ 3.308773 × 10⁻⁶ = 8.523 Ω/km (2.598 Ω/1000 ft). 100 m: 0.8523 Ω.
  • Weight: copper 8.96 × 3.308773 = 29.65 kg/km (19.92 lb/1000 ft), so 100 m weighs 2.965 kg; aluminium 2.70 × 3.308773 = 8.934 kg/km.
  • Close-wound: 1 ÷ 0.08081 in = 12.4 turns per inch of bare wire (enamel adds a little).

At 75 °C copper resistance is 1 + 0.00393 × 55 = 1.21615 times higher: 5.2104 × 1.21615 = 6.337 Ω/km. Going the other way, 2.5 mm² is a diameter of √(4 × 2.5 ÷ π) = 1.784 mm, which is 36 − 39 × log(1.784 ÷ 0.127) ÷ log(92) = 13.21 AWG, so the nearest gauge is 13 AWG and the common one just bigger is 12 AWG.

Metric sizes (IEC 60228) in AWG

mm²Solid diameter mmExact AWGkcmilCopper Ω/km at 20 °CAluminium Ω/km
0.50.79820.150.9934.4856.4
0.750.97718.41.4822.9937.6
11.12817.161.9717.2428.2
1.51.38215.412.9611.4918.8
2.51.78413.214.936.89611.28
42.25711.187.894.317.05
62.7649.4311.842.8734.7
103.5687.2319.741.7242.82
164.5145.231.581.0781.763
255.6423.2849.340.68961.128
356.6761.8369.070.49260.8057
507.9791/0 (0.29)98.680.34480.564
709.4412/0 (-1.16)138.150.24630.4029
9510.9983/0 (-2.48)187.480.18150.2968
12012.361237 kcmil236.820.14370.235
15013.82296 kcmil296.030.11490.188
18515.348365 kcmil365.10.093190.1524
24017.481474 kcmil473.650.071830.1175
30019.544592 kcmil592.060.057470.094
40022.568789 kcmil789.410.04310.0705
50025.231987 kcmil986.760.034480.0564
63028.3221,243 kcmil1,243.320.027370.04476
80031.9151,579 kcmil1,578.820.021550.03525
100035.6821,974 kcmil1,973.530.017240.0282

Resistance from resistivity for plain solid metal. IEC 60228 and cable datasheets give the maximum resistance for real (often stranded) conductors, which is a few % higher, for example 7.41 Ω/km for 2.5 mm² copper against 6.90 Ω/km here. Use the datasheet when it matters.

Solid or stranded

  • A gauge or mm² size is the area of metal. A stranded wire of the same size has the same metal but is wider across, because round strands leave gaps (often 5–15% wider).
  • Stranded cables are made to a set number of strands, for example 7 strands for 2.5 mm² building wire, or many fine strands for flexible cords. The strand diameter alone gives the area: use Stranded wire in Advanced.
  • Twisting makes each strand a little longer than the cable, so resistance per metre is a few % higher than for solid wire.

What this doesn't tell you

It doesn't give a current rating (ampacity). How much current a wire can carry without overheating depends on the wiring code where you are, the insulation's temperature rating, whether it's in a wall, conduit, buried or in free air, how many cables run together and the room temperature. Check your local rules or ask a qualified electrician, and use the voltage drop calculator to see how much a long run loses.

Common questions

How do you convert AWG to mm²?

First find the diameter: d (inches) = 0.005 × 92^((36 − AWG) ÷ 39), or d (mm) = 0.127 × 92^((36 − AWG) ÷ 39). Then area = π ÷ 4 × d². For 12 AWG: d = 2.053 mm and area = 0.7854 × 2.053² = 3.309 mm².

What is 2.5 mm² in AWG?

2.5 mm² is a diameter of 1.784 mm, which works out to 13.2 AWG. The nearest size is 13 AWG (2.63 mm²), but 13 is rarely sold, so in practice 12 AWG (3.31 mm²) is the usual choice and 14 AWG (2.08 mm²) is smaller.

What do 1/0, 2/0, 3/0 and 4/0 mean?

They are the gauges thicker than 1 AWG, also written 0, 00, 000 and 0000. In the formula use 0, −1, −2 and −3. 4/0 is exactly 0.46 inch across (11.68 mm, 107.2 mm²). Beyond 4/0, wire is sized in kcmil (thousands of circular mils).

What is a circular mil?

A circular mil is the area of a circle 1 mil (one thousandth of an inch) across. A round wire's area in circular mils is simply its diameter in mils squared, so 12 AWG (80.81 mil) is 6,530 circular mils. 1 kcmil = 1,000 circular mils = 0.5067 mm².

How much current can a wire carry?

This calculator doesn't give current ratings (ampacity). The safe current depends on your country's wiring code, the insulation, how the cable is run, how many cables are bunched together and the room temperature. Use your local wiring rules or ask an electrician, and use the voltage drop calculator to check long runs.

Is stranded wire the same size as solid wire?

Gauges and mm² sizes describe the metal area, not the outside size. A stranded wire has gaps between strands, so it is a little wider than a solid wire with the same area, and its resistance is often a few % higher because the strands are slightly longer than the cable.

Related calculators

Voltage drop calculatorVoltage drop and wire size for DC, single and three phase: volts and % lost, voltage at the load, power lost as heat, copper or aluminium in mm² or AWG, conductor temperature, power factor and the smallest size that stays under your % limit.Ohm's Law CalculatorAny two of voltage, current, resistance and power give the other two, with the formula used on the Ohm's law wheel, series and parallel resistors, LED resistor, voltage divider and AC power.kVA, kW and Amps ConverterConvert between kVA, kW, amps and horsepower for single phase, three phase and DC: power factor, kVAR, VA, BTU/h, motor input from shaft horsepower and a table of amps for common kVA sizes.Resistor Color Code CalculatorResistor colour bands to ohms and back for 3, 4, 5 and 6 bands: tolerance range, temperature coefficient, nearest E-series value, SMD codes and series/parallel.

Made by Zulu Calculator, part of AlphaZulu LLC. Formulas are shown in full and rule figures are checked against official sources; see how we build calculators.

Embed this calculator on your site

Free to use on your website or blog. Paste this code where you want the calculator to appear. Please keep the credit link.

Wire Gauge Calculator by Zulu Calculator ↗