Voltage Drop Calculator
See how many volts a cable loses, the voltage left at the load and the smallest wire size in mm² or AWG that keeps the drop under your limit. Advanced adds temperature, power factor, reactance and parallel cables.
For three phase, enter the line-to-line voltage (for example 400 V or 480 V).
Many standards use limits of around 3–5%. Check the rules where you live.
Two or more identical cables sharing the current, as on big feeders.
Resistance rises as wire warms up. 20 °C is the reference; a cable carrying its full rated current runs much warmer, often 70 °C for PVC or 90 °C for XLPE insulation, so 70–75 °C gives a more cautious answer.
Used to turn watts into amps on AC, and for the reactance method. About 1 for heaters and lights, 0.8–0.9 for motors. Simple mode uses 1.
Multicore cables are often around 0.07–0.1 Ω/km; check your cable's datasheet. Reactance matters most on big cables.
Resistance only is what Simple mode uses: it ignores power factor and reactance, which usually gives the same or a slightly higher drop. The second method uses drop = k × L × I × (R × PF + X × sin φ).
Voltage drop only. This doesn't check whether the cable can carry the current safely (its current rating or ampacity, which depends on how it's installed) or the breaker or fuse. Follow your local wiring rules and use a qualified electrician.
Drop for every wire size
| Size | mm² | Drop | % | Lost | Within limit |
|---|
How your voltage drop is worked out
Find the wire's resistance per metre, multiply by the length the current travels and by the current, then compare the drop with the supply.
- 1
Wire resistance
ρ copper, 20 °C÷ 2.5 mm²= 6.896 mΩ/m
- 2
Wire the current runs
2 × 30 m= 60 m of wire
- 3
Volts lost
60 m × 6.896 mΩ× 20 A= 8.28 V
- 4
Share of supply
8.28 V ÷ 230 V= 3.6% drop→ 4 mm² for 3%
Read more: the formula, a worked example, wire sizes, AWG to mm² and what this doesn't check
Each wire has a small resistance that grows with its length and shrinks with its cross-section. The current has to go out to the load and come back, so on DC and single phase it passes through twice the one-way length. Multiply that resistance by the current and you have the volts lost on the way.
The formula
resistivity at T = resistivity at 20 °C × (1 + α × (T − 20))
resistance per metre (R) = resistivity ÷ cross-section area
DC and single phase: drop = 2 × one-way length × current × R
three phase: drop = √3 × one-way length × current × R
with power factor and reactance: use (R × PF + X × sin φ) in place of R
drop % = drop ÷ supply voltage × 100
voltage at the load = supply voltage − drop
power lost = current² × R × length × number of live wires (2, or 3 on three phase)
current from watts = watts ÷ (volts × PF), or ÷ (1.732 × volts × PF) on three phase
Copper: resistivity 1.724 × 10⁻⁸ Ω·m at 20 °C, α = 0.00393 per °C. Aluminium: 2.82 × 10⁻⁸ Ω·m, α = 0.00403 per °C. 1 mm² = 10⁻⁶ m².
Worked example
A 20 A load on 230 V single phase, 30 m from the board, on 2.5 mm² copper at 20 °C, with a 3% limit.
- Resistance per metre: 1.724 × 10⁻⁸ ÷ 2.5 × 10⁻⁶ = 0.006896 Ω/m (6.896 Ω/km).
- Wire the current runs: 2 × 30 = 60 m, so the loop is 60 × 0.006896 = 0.41376 Ω.
- Voltage drop: 60 × 0.006896 × 20 = 8.2752 V, about 8.28 V.
- As a share: 8.2752 ÷ 230 × 100 = 3.598%, over the 3% limit.
- Voltage at the load: 230 − 8.2752 = 221.72 V.
- Power lost: 20² × 0.006896 × 30 × 2 = 8.2752 × 20 = 165.50 W, which is 3.6% of the 230 × 20 = 4,600 W load.
- Next size up, 4 mm²: 1.724 × 10⁻⁸ ÷ 4 × 10⁻⁶ = 0.00431 Ω/m; 60 × 0.00431 × 20 = 5.172 V = 5.172 ÷ 230 = 2.25%, so 4 mm² is the smallest size within 3%.
- Longest run on 2.5 mm² for 3%: 3% of 230 V = 6.9 V; 6.9 ÷ (2 × 20 × 0.006896 = 0.27584) = 25.01 m.
At a conductor temperature of 75 °C the resistance is 1 + 0.00393 × 55 = 1.21615 times higher, so the drop becomes 8.2752 × 1.21615 = 10.06 V (4.38%). The same run in aluminium 2.5 mm² at 20 °C: 2.82 × 10⁻⁸ ÷ 2.5 × 10⁻⁶ = 0.01128 Ω/m, so 60 × 0.01128 × 20 = 13.536 V (5.89%).
Three phase example: 32 A at 400 V over 50 m of 6 mm² copper: 1.732 × 50 × 32 × 0.0028733 = 7.96 V, which is 1.99% of 400 V.
Resistance of common metric sizes
| Size | Copper Ω/km at 20 °C | Copper at 70 °C | Aluminium at 20 °C |
|---|---|---|---|
| 1 mm² | 17.24 | 20.6277 | 28.2 |
| 1.5 mm² | 11.4933 | 13.7518 | 18.8 |
| 2.5 mm² | 6.896 | 8.2511 | 11.28 |
| 4 mm² | 4.31 | 5.1569 | 7.05 |
| 6 mm² | 2.8733 | 3.4379 | 4.7 |
| 10 mm² | 1.724 | 2.0628 | 2.82 |
| 16 mm² | 1.0775 | 1.2892 | 1.7625 |
| 25 mm² | 0.6896 | 0.8251 | 1.128 |
| 35 mm² | 0.4926 | 0.5894 | 0.8057 |
| 50 mm² | 0.3448 | 0.4126 | 0.564 |
| 70 mm² | 0.2463 | 0.2947 | 0.4029 |
| 95 mm² | 0.1815 | 0.2171 | 0.2968 |
| 120 mm² | 0.1437 | 0.1719 | 0.235 |
| 150 mm² | 0.1149 | 0.1375 | 0.188 |
| 185 mm² | 0.0932 | 0.1115 | 0.1524 |
| 240 mm² | 0.0718 | 0.0859 | 0.1175 |
| 300 mm² | 0.0575 | 0.0688 | 0.094 |
| 400 mm² | 0.0431 | 0.0516 | 0.0705 |
| 500 mm² | 0.0345 | 0.0413 | 0.0564 |
| 630 mm² | 0.0274 | 0.0327 | 0.0448 |
Worked out from resistivity for solid, plain conductors. Real stranded cables are a little different (standard tables such as IEC 60228 give a maximum, for example 7.41 Ω/km for 2.5 mm² copper), so use the datasheet figure in Advanced when you have it.
AWG to mm²
American Wire Gauge diameter: d = 0.127 mm × 92^((36 − AWG) ÷ 39), and area = π ÷ 4 × d². For 1/0, 2/0, 3/0 and 4/0 use 0, −1, −2 and −3. Bigger sizes are given in kcmil (thousands of circular mils): 1 kcmil = 0.5067 mm².
| Size | Area mm² | Copper Ω/1000 ft at 20 °C |
|---|---|---|
| 22 AWG | 0.326 | 16.1419 |
| 20 AWG | 0.518 | 10.1518 |
| 18 AWG | 0.823 | 6.3845 |
| 16 AWG | 1.309 | 4.0153 |
| 14 AWG | 2.081 | 2.5252 |
| 12 AWG | 3.309 | 1.5881 |
| 10 AWG | 5.261 | 0.9988 |
| 8 AWG | 8.366 | 0.6281 |
| 6 AWG | 13.302 | 0.395 |
| 4 AWG | 21.151 | 0.2484 |
| 3 AWG | 26.67 | 0.197 |
| 2 AWG | 33.631 | 0.1562 |
| 1 AWG | 42.408 | 0.1239 |
| 1/0 AWG | 53.475 | 0.0983 |
| 2/0 AWG | 67.431 | 0.0779 |
| 3/0 AWG | 85.029 | 0.0618 |
| 4/0 AWG | 107.219 | 0.049 |
| 250 kcmil | 126.677 | 0.0415 |
| 300 kcmil | 152.012 | 0.0346 |
| 350 kcmil | 177.348 | 0.0296 |
| 400 kcmil | 202.683 | 0.0259 |
| 500 kcmil | 253.354 | 0.0207 |
| 600 kcmil | 304.024 | 0.0173 |
| 750 kcmil | 380.031 | 0.0138 |
| 1000 kcmil | 506.707 | 0.0104 |
How much drop is OK?
There is no single world rule. Many national wiring standards and guides use limits of around 3% to 5% from the supply to the furthest point, sometimes split between the main feeder and the final circuit, and some equipment (motors starting, LED drivers, long low-voltage DC runs for solar or boats) needs less. Use the limit your local wiring rules give for your type of circuit.
What this doesn't check
- Current rating (ampacity): a cable must carry the current without overheating. That depends on the insulation, how it's run (in a wall, conduit, buried, in free air), how many cables are bunched together and the room temperature. A size that passes for voltage drop can still be too small to be safe.
- Protection: the breaker or fuse must suit the cable and the load, and the circuit must disconnect fast enough in a fault.
- Starting current: motors draw several times their running current for a moment, so the drop while starting is much bigger.
This calculator uses physics, not any one country's wiring tables. Electrical work is regulated in most places: follow your local rules and have a qualified electrician design and check the installation.
Common questions
What is voltage drop?
Every wire has a little resistance, so some of the supply voltage is used up pushing the current along the cable and turns into heat. The longer and thinner the cable, and the bigger the current, the more volts are lost before the power reaches the load.
How do you calculate voltage drop?
For DC and single phase: voltage drop = 2 × one-way length × current × resistance per metre. For three phase: √3 × length × current × resistance per metre. Resistance per metre = resistivity ÷ cross-section area. 20 A over 30 m of 2.5 mm² copper drops 2 × 30 × 20 × 0.006896 = 8.28 V, which is 3.6% of 230 V.
What is an acceptable voltage drop?
Many wiring standards and guides use limits of around 3% to 5%, often split between the feeder and the final circuit, but the exact figure depends on the country, the type of circuit and the equipment. Check your local wiring rules, or ask a licensed electrician.
What size wire do I need to keep voltage drop down?
Enter your current, voltage, one-way length and your % limit: the calculator tries every standard size and picks the smallest that stays within the limit. For 20 A at 230 V over 30 m with a 3% limit, 2.5 mm² copper gives 3.6%, so 4 mm² (2.25%) is needed.
Does this calculator check if the cable can carry the current?
No. It works out voltage drop only. A cable must also be big enough to carry the current without overheating (its current rating or ampacity, which depends on how it's installed, grouped and insulated), and be protected by the right breaker or fuse. Use your local wiring rules or an electrician for those.
Why is aluminium wire bigger than copper for the same job?
Aluminium's resistivity is about 2.82 × 10⁻⁸ Ω·m against copper's 1.724 × 10⁻⁸ Ω·m, so it has about 1.64 times the resistance for the same size. To get the same voltage drop you need roughly 1.64 times the cross-section, usually the next standard size or two up.