Voltage Drop Calculator

See how many volts a cable loses, the voltage left at the load and the smallest wire size in mm² or AWG that keeps the drop under your limit. Advanced adds temperature, power factor, reactance and parallel cables.

More options
Supply
V
A

For three phase, enter the line-to-line voltage (for example 400 V or 480 V).

m
Wire metal
%

Many standards use limits of around 3–5%. Check the rules where you live.

Wire details
°C

Two or more identical cables sharing the current, as on big feeders.

Resistance rises as wire warms up. 20 °C is the reference; a cable carrying its full rated current runs much warmer, often 70 °C for PVC or 90 °C for XLPE insulation, so 70–75 °C gives a more cautious answer.

AC details
PF

Used to turn watts into amps on AC, and for the reactance method. About 1 for heaters and lights, 0.8–0.9 for motors. Simple mode uses 1.

Method

Resistance only is what Simple mode uses: it ignores power factor and reactance, which usually gives the same or a slightly higher drop. The second method uses drop = k × L × I × (R × PF + X × sin φ).

ResultUpdates as you type—Voltage drop—Drop as % of supply—Voltage at the load—Power lost in the cable—Smallest size under 3%—Longest run for 3%—Wire resistance

Voltage drop only. This doesn't check whether the cable can carry the current safely (its current rating or ampacity, which depends on how it's installed) or the breaker or fuse. Follow your local wiring rules and use a qualified electrician.

Drop for every wire size
Sizemm²Drop%LostWithin limit

How your voltage drop is worked out

Find the wire's resistance per metre, multiply by the length the current travels and by the current, then compare the drop with the supply.

  1. 1

    Wire resistance

    ρ copper, 20 °C÷ 2.5 mm²= 6.896 mΩ/m

  2. 2

    Wire the current runs

    2 × 30 m= 60 m of wire

  3. 3

    Volts lost

    60 m × 6.896 mΩ× 20 A= 8.28 V

  4. 4

    Share of supply

    8.28 V ÷ 230 V= 3.6% drop→ 4 mm² for 3%

Read more: the formula, a worked example, wire sizes, AWG to mm² and what this doesn't check

Each wire has a small resistance that grows with its length and shrinks with its cross-section. The current has to go out to the load and come back, so on DC and single phase it passes through twice the one-way length. Multiply that resistance by the current and you have the volts lost on the way.

The formula

resistivity at T = resistivity at 20 °C × (1 + α × (T − 20))
resistance per metre (R) = resistivity ÷ cross-section area
DC and single phase: drop = 2 × one-way length × current × R
three phase: drop = √3 × one-way length × current × R
with power factor and reactance: use (R × PF + X × sin φ) in place of R
drop % = drop ÷ supply voltage × 100
voltage at the load = supply voltage − drop
power lost = current² × R × length × number of live wires (2, or 3 on three phase)
current from watts = watts ÷ (volts × PF), or ÷ (1.732 × volts × PF) on three phase

Copper: resistivity 1.724 × 10⁻⁸ Ω·m at 20 °C, α = 0.00393 per °C. Aluminium: 2.82 × 10⁻⁸ Ω·m, α = 0.00403 per °C. 1 mm² = 10⁻⁶ m².

Worked example

A 20 A load on 230 V single phase, 30 m from the board, on 2.5 mm² copper at 20 °C, with a 3% limit.

  • Resistance per metre: 1.724 × 10⁻⁸ ÷ 2.5 × 10⁻⁶ = 0.006896 Ω/m (6.896 Ω/km).
  • Wire the current runs: 2 × 30 = 60 m, so the loop is 60 × 0.006896 = 0.41376 Ω.
  • Voltage drop: 60 × 0.006896 × 20 = 8.2752 V, about 8.28 V.
  • As a share: 8.2752 ÷ 230 × 100 = 3.598%, over the 3% limit.
  • Voltage at the load: 230 − 8.2752 = 221.72 V.
  • Power lost: 20² × 0.006896 × 30 × 2 = 8.2752 × 20 = 165.50 W, which is 3.6% of the 230 × 20 = 4,600 W load.
  • Next size up, 4 mm²: 1.724 × 10⁻⁸ ÷ 4 × 10⁻⁶ = 0.00431 Ω/m; 60 × 0.00431 × 20 = 5.172 V = 5.172 ÷ 230 = 2.25%, so 4 mm² is the smallest size within 3%.
  • Longest run on 2.5 mm² for 3%: 3% of 230 V = 6.9 V; 6.9 ÷ (2 × 20 × 0.006896 = 0.27584) = 25.01 m.

At a conductor temperature of 75 °C the resistance is 1 + 0.00393 × 55 = 1.21615 times higher, so the drop becomes 8.2752 × 1.21615 = 10.06 V (4.38%). The same run in aluminium 2.5 mm² at 20 °C: 2.82 × 10⁻⁸ ÷ 2.5 × 10⁻⁶ = 0.01128 Ω/m, so 60 × 0.01128 × 20 = 13.536 V (5.89%).

Three phase example: 32 A at 400 V over 50 m of 6 mm² copper: 1.732 × 50 × 32 × 0.0028733 = 7.96 V, which is 1.99% of 400 V.

Resistance of common metric sizes

SizeCopper Ω/km at 20 °CCopper at 70 °CAluminium at 20 °C
1 mm²17.2420.627728.2
1.5 mm²11.493313.751818.8
2.5 mm²6.8968.251111.28
4 mm²4.315.15697.05
6 mm²2.87333.43794.7
10 mm²1.7242.06282.82
16 mm²1.07751.28921.7625
25 mm²0.68960.82511.128
35 mm²0.49260.58940.8057
50 mm²0.34480.41260.564
70 mm²0.24630.29470.4029
95 mm²0.18150.21710.2968
120 mm²0.14370.17190.235
150 mm²0.11490.13750.188
185 mm²0.09320.11150.1524
240 mm²0.07180.08590.1175
300 mm²0.05750.06880.094
400 mm²0.04310.05160.0705
500 mm²0.03450.04130.0564
630 mm²0.02740.03270.0448

Worked out from resistivity for solid, plain conductors. Real stranded cables are a little different (standard tables such as IEC 60228 give a maximum, for example 7.41 Ω/km for 2.5 mm² copper), so use the datasheet figure in Advanced when you have it.

AWG to mm²

American Wire Gauge diameter: d = 0.127 mm × 92^((36 − AWG) ÷ 39), and area = π ÷ 4 × d². For 1/0, 2/0, 3/0 and 4/0 use 0, −1, −2 and −3. Bigger sizes are given in kcmil (thousands of circular mils): 1 kcmil = 0.5067 mm².

SizeArea mm²Copper Ω/1000 ft at 20 °C
22 AWG0.32616.1419
20 AWG0.51810.1518
18 AWG0.8236.3845
16 AWG1.3094.0153
14 AWG2.0812.5252
12 AWG3.3091.5881
10 AWG5.2610.9988
8 AWG8.3660.6281
6 AWG13.3020.395
4 AWG21.1510.2484
3 AWG26.670.197
2 AWG33.6310.1562
1 AWG42.4080.1239
1/0 AWG53.4750.0983
2/0 AWG67.4310.0779
3/0 AWG85.0290.0618
4/0 AWG107.2190.049
250 kcmil126.6770.0415
300 kcmil152.0120.0346
350 kcmil177.3480.0296
400 kcmil202.6830.0259
500 kcmil253.3540.0207
600 kcmil304.0240.0173
750 kcmil380.0310.0138
1000 kcmil506.7070.0104

How much drop is OK?

There is no single world rule. Many national wiring standards and guides use limits of around 3% to 5% from the supply to the furthest point, sometimes split between the main feeder and the final circuit, and some equipment (motors starting, LED drivers, long low-voltage DC runs for solar or boats) needs less. Use the limit your local wiring rules give for your type of circuit.

What this doesn't check

  • Current rating (ampacity): a cable must carry the current without overheating. That depends on the insulation, how it's run (in a wall, conduit, buried, in free air), how many cables are bunched together and the room temperature. A size that passes for voltage drop can still be too small to be safe.
  • Protection: the breaker or fuse must suit the cable and the load, and the circuit must disconnect fast enough in a fault.
  • Starting current: motors draw several times their running current for a moment, so the drop while starting is much bigger.

This calculator uses physics, not any one country's wiring tables. Electrical work is regulated in most places: follow your local rules and have a qualified electrician design and check the installation.

Common questions

What is voltage drop?

Every wire has a little resistance, so some of the supply voltage is used up pushing the current along the cable and turns into heat. The longer and thinner the cable, and the bigger the current, the more volts are lost before the power reaches the load.

How do you calculate voltage drop?

For DC and single phase: voltage drop = 2 × one-way length × current × resistance per metre. For three phase: √3 × length × current × resistance per metre. Resistance per metre = resistivity ÷ cross-section area. 20 A over 30 m of 2.5 mm² copper drops 2 × 30 × 20 × 0.006896 = 8.28 V, which is 3.6% of 230 V.

What is an acceptable voltage drop?

Many wiring standards and guides use limits of around 3% to 5%, often split between the feeder and the final circuit, but the exact figure depends on the country, the type of circuit and the equipment. Check your local wiring rules, or ask a licensed electrician.

What size wire do I need to keep voltage drop down?

Enter your current, voltage, one-way length and your % limit: the calculator tries every standard size and picks the smallest that stays within the limit. For 20 A at 230 V over 30 m with a 3% limit, 2.5 mm² copper gives 3.6%, so 4 mm² (2.25%) is needed.

Does this calculator check if the cable can carry the current?

No. It works out voltage drop only. A cable must also be big enough to carry the current without overheating (its current rating or ampacity, which depends on how it's installed, grouped and insulated), and be protected by the right breaker or fuse. Use your local wiring rules or an electrician for those.

Why is aluminium wire bigger than copper for the same job?

Aluminium's resistivity is about 2.82 × 10⁻⁸ Ω·m against copper's 1.724 × 10⁻⁸ Ω·m, so it has about 1.64 times the resistance for the same size. To get the same voltage drop you need roughly 1.64 times the cross-section, usually the next standard size or two up.

Related calculators

Wire Gauge CalculatorAWG to mm² and back: diameter in mm, inches and mils, cross-section in mm², circular mils and kcmil, nearest metric and AWG size, stranded wire, copper and aluminium resistance per km or 1000 ft at any temperature, weight and a full 4/0 to 40 AWG table.Ohm's Law CalculatorAny two of voltage, current, resistance and power give the other two, with the formula used on the Ohm's law wheel, series and parallel resistors, LED resistor, voltage divider and AC power.Generator size calculatorThe generator size in kW and kVA for home or business backup: appliances with running and starting watts, the surge peak, safety margin, power factor, amps on single or three phase, fuel use, runtime on a tank and inverter battery size.Solar panel calculatorSolar system size in kW, number of panels, roof area, yearly kWh, savings and payback from your use or bill and your peak sun hours, with slab-aware Gulf tariffs, net metering or export, 25-year savings, NPV, CO₂ and a backup battery.

Made by Zulu Calculator, part of AlphaZulu LLC. Formulas are shown in full and rule figures are checked against official sources; see how we build calculators.

Embed this calculator on your site

Free to use on your website or blog. Paste this code where you want the calculator to appear. Please keep the credit link.

Voltage drop calculator by Zulu Calculator ↗